Modern data centers consume far less water than previously believed, largely due to technological advancements like direct-to-chip liquid cooling and closed-loop systems. Historically, evaporative cooling used significant water for energy efficiency, but today’s designs prioritize high-temperature heat rejection, reducing the need for water-intensive cooling towers. Most data centers now operate with minimal evaporation, relying instead on efficient heat transfer and dry coolers for peak loads. While construction and startup phases require some water for pipe filling and cleaning, this is typically reused on-site, minimizing environmental impact. The perception that data centers drain aquifers stems from outdated numbers and misaligned context—agriculture and urban development consume far more water. The industry acknowledges that transparency in communication is key to easing community concerns, as demonstrated by Microsoft’s proactive messaging in Wisconsin. Ultimately, data center water use is a small fraction of broader water consumption, and the future lies in continued innovation, efficiency, and public education to address misconceptions and build trust.
I'm Shail Khan. I lead early-stage investments at Energy Impact Partners. Welcome to Catalyst.
So of all the fights over data centers, I think water might be the one where the two sides sort
of talk past each other the most. Opponents say data centers are draining aquifers and competing
with towns for drinking water. Proponents basically say it's a nothing burger. It's a
rounding error next to agriculture and other major water consumers. And actually, new data
centers barely use any water at all. I think there are two things going on here. The first is about
context. So say a 300-megawatt data center with evaporative cooling uses like 150 million gallons
of water per year. Is that a big number or a small number? Just for context, a combined cycle power
plant of the same capacity would use roughly three times as much water. Or actually, maybe even
better, 150 million gallons per year is about three times as much water per year.
The second, though, is about history versus future. I think even the data center industry
would admit that water consumption was significantly higher in the past. But I'll also tell you that
modern designs, which might be closed-loop, consume very little water at all, perhaps down
to essentially just restrooms and kitchens. So rather than trying to argue the numbers,
I wanted to understand where the water actually goes.
What inside a data center needs cooling? What is the challenge there? How did we do it
historically? And what's changed now that a single rack can draw what used to power a whole row?
It turns out that the answer to how much water the data center consumes is actually mostly a design
choice. But it's a design choice being made right now at gigawatt scale, and the old numbers don't
actually tell you much about the way it's going. So to walk through it, I talked to Tim Shedd,
the founder of Abolient Insights and an
expert in data center cooling. That's coming up next.
Tim Shedd:
I'm Tim Shedd, and I'm the founder of Abolient Insights and an expert in data center cooling.
And today, I'm going to talk to Tim Shedd about how data center cooling works and how it's
designed.
So today, I'm going to talk to Tim Shedd about how data center cooling works and how it's
designed.
I'm Tim Shedd, and I'm the founder of Abolient Insights and an expert in data center cooling.
Tim Shedd:
So today, I'm going to talk to Tim Shedd about how data center cooling works and how it's
designed.
So today, I'm going to talk to Tim Shedd about how data center cooling works and how it's
to every server for every watt that i'm trying to cool and at some point that kind of breaks down
um at least from that model so what we did to start to try to make things more efficient as
we went from nine kilowatts to some high performance computing going to 30 kilowatts
and 40 kilowatts a rack is put an in-row cooler next to it so we bring the cooling
closer to the heat source that saves me a lot of energy actually a rear door heat exchanger
or an in-row cooler they're have kind of the same basic concept of just bringing that heat
exchanger as close as possible to the heat source that way my fans are working very efficiently
because i'm only moving heat really closely to my compute and i'm only using fan power that i need
and if the racks next to or attached to the radar heat exchanger don't need to be cooled
the fans dial back and i'm saving a lot of energy actually but that requires plumbing now
onto the the data center floor uh made some people uncomfortable but overall you know it's a good idea
but even that gets limited at about 80 kilowatts we've you know i was working for dell and we
shipped racks regularly at up to 80 kilowatts a rack with rear door heat exchangers but beyond
that it gets difficult to pull enough air through to cool so that's what brings us to today it's not
you know radar heat exchangers are actually really efficient and um in many cases almost as efficient
as direct liquid cooling up to that power amount but beyond that it just starts to get really
difficult okay so to bring it forward to today then you said you know you were shipping 80
kilowatt racks at dell where are we today like what are the in in a new state-of-the-art frontier
inference or training data center like what's the rack density everybody probably listening to this
podcast is aware of the virarubin mvl 72 or vr mvl 72 racks those are rated at 220 kilowatts a rack
including the power supplies and everything else so um that's a lot of power in iraq but that's
actually not the densest racks that are shipping today um as an example um dell is installing the
uh dudna um super computing cluster at lawrence berkeley national labs and and that power level
kept creeping up i want to say it's about 280 kilowatts in iraq um but i i don't remember that
exactly but my point is that that 220 kilowatts is actually not the limit today um there there
are ways to keep packing more and more uh gpus into a a rack um even today and um whether they're
100 percent liquid cooled like the mvl 72 or they're a mix of air cooling and liquid cooling
like the um the dude in the supercomputer um we can still manage that level in fact we can manage
we've we've mapped out up to 400 plus kilowatts um 500 kilowatts in that rack so um
that is what's possible today uh from a cooling perspective
and from a power delivery perspective using orv3 uh racks and so on so yeah we should expect to see
that type of density uh continuing on right presumption would be that and density continues
to increase that's the direction of travel and regardless it's a you know to your point like
we could do 80 kilowatts air cooled maybe we could squeak out a little bit more than that regardless
we're multiple of that now so clearly we are forced into doing something other than air
cooling which is liquid cooling so walk me through the mechanism what is what is liquid
cooling actually look like in iraq and then and then we should talk about the water side of it
ultimately what we have to do is bring water to every device that needs to be cooled
with liquid so the reason i qualify that is there are different architectures for
servers today some are like the the eight-way uh dgx uh architectures
today those are still typically a hybrid cooled solution so the gpus and and
mv link and other devices are cooled with water but storage might still be air cooled
network cards might still be air cooled and so on so i'm going to have some mix of airflow
through the server as well as as liquid and in other cases like the mbl 72
it's 100 liquid cooled so i'm bringing water into the server and having to route it to
every device somehow touching every device greater than about a half a watt
so it's a really intense process once we decide that everything's going to be liquid cooled
so imagine just it's a plumbing problem i've got two ports and then a supply and a return on the
server and i've got to route that liquid to every cold plate to every piece of copper basically with
enhanced you know with fins on it that i'm going to run the water through to pull the heat off of
of all the hot devices in addition we typically want to make this serviceable so in other words
we want to make it so that we can remove one gpu out of eight or four that are in there that means
that all those liquid connections have to have some sort of connector that allows us to remove
the gpu without spilling liquid all over the place so in addition to the plumbing to just connect all
the copper together that we're using to cool the the the processors we also have manifolds and we
have quick connects and we have hoses and other things so there's it's the the liquid cooling
infrastructure is actually quite significant and takes up a significant volume within the server
today so um as far as the the cold plates themselves they are essentially um just think
of it as a as a basically a piece of two million and a half pounds of liquid cooling infrastructure
of two millimeter thick copper maybe it's one one and a half millimeters depending and then we've
um generally created uh people call them different things but skived fins or fins that are made by
shaving a bit of copper off the surface and flipping it up um and uh the typical spacing is
about 100 microns thick for the copper and about 100 microns spacing between um i in historically
we call those micro channels micro channel cooling today has a different connotation
we can dive into that if we want but um they're typically about three millimeters tall
and we're going to try to arrange them such that we're flowing water through
every one of those micro channels and pulling heat off and that's non-trivial
but if we do so they're very high performance we can now cool a you know 1400 watt 1800 watt processor
using 1400 or 1800 watt processors that are very high performance and we can now cool a you know 1400 watt 1800 watt processor
and uh that's non-trivial but if we do so they're very high performance we can now cool a you know 1400 watt 1800 watt processors
using 45 degree c water that's phenomenal that's actually something we couldn't do three years ago
so a lot of progress has been made um and then a lot of additional technology and figuring out
how to seal those things so they don't you know they don't leak easily they can be shipped across
the oceans and and not burst or have any other problems there's a lot a lot of engineering has
gone into the cold plates in a pretty short time to make them reliable and high performance can
you orient me a little bit on there's different architectures within liquid cooling and you hear
these different terms just give me like the the sense of direct-to-chip cooling immersion cooling
people talk about two-phase like what how should i think about categorizing the different ways to do
liquid cooling uh direct-to-chip means bringing the coolant to the chip and so i structure chip
and that can be either single phase or two phase um so um the most the dominant form today is single
phase direct-to-chip cooling using water with 25 propylene glycol mixed in so it's basically
um crudely speaking it's basically the antifreeze that you pour into your car diluted to 25 when you
go buy it at the um auto parts store it's often 50 next premix the really important detail that
you don't even think about when you go pick up a bottle of antifreeze is that that
you have a very small percentage about one percent to two percent maybe of a proprietary chemical
mix it's called an inhibitor or inhibitor package that prevents corrosion so your car has aluminum
and brass and all sorts of other materials in it and lasts for years without corroding and falling
apart that's actually phenomenal that's amazing so our partners at you know like valvoline and dao and
ricocam and they've done an amazing job developing these these coolants that are very long lasting
and allow us to use many different materials in in their systems that's the same thing we have to pay
attention to in the single phase liquid cooling system so um that's single phase liquid cooling
two-phase liquid cooling is not yet really available at scale there are companies working on
it i myself had a company that worked on this um so i'm a little you know hesitant to say that i'm a
big fan of this um so i'm a little you know have some some history with this um but there are
definitely um products that are very close to commercialization in this space and it's where
you take a refrigerant you pump it to the chip and you literally boil the refrigerant off of
the chips uh you know off of the fins um it looks really cool bubbles are great uh it turns out that
that the performance is very similar
to single-phase. It's not really
superior in performance, but there are other
benefits. I can use much smaller hoses and
tubes and so on. So remember I was saying
currently the DLC
takes up a lot of real estate inside of the
servers. Two-phase promises,
again, not mass-adopted
yet, but promises to use a lot
less space inside of the servers, leaving more
space for innovation on the actual
compute. Immersion
can take two forms, in single-phase
and two-phase. In single-phase,
we use an immersion
fluid, a coolant,
that is often
derived from something like mineral oil,
but it's generally much more sophisticated
than this, and
has additives and other
inhibitors as well.
The problem with oil is
if you can imagine
it's a hot day and you're
getting excited, you jump in the pool and that pool is filled
with oil, that would feel pretty not
great. It wouldn't cool you off, right? Because
oil is actually itself a pretty poor
heat transfer fluid.
And so, it turns out that
it's just not
it's good for
picking up low-density
heat from a large area.
It's not great for picking
up heat from the
high-performance processors.
And so, to do that,
they're proposing, the
immersion community is proposing
putting cold plates on
the chips themselves and then picking up all the rest
of the heat from those small
devices with this
immersion fluid.
And there are pros and cons to that, but that's
kind of the trajectory that they're on.
Two-phase immersion
is coming and
going and coming again, maybe.
The challenge with that is
I need to
be able to have a fluid that boils
and doesn't get,
doesn't allow the combination
of vapor and liquid together in a container
to get at too high of a pressure.
It gets a little complicated here,
but that boiling
point of that fluid really matters because
if the pressure rises even
to a third
of an atmosphere
and I'm in a great big tank,
that can create a lot of force on the lid
and create a negative
very bad situation.
So, I have to manage
that vapor, I have to manage the expansion
and it's a little complicated there
and there are other things we actually published
me and two colleagues published a paper on
this about four years ago,
three and a half years ago now that went into some of the
details of the limitations
of two-phase immersion and it's
again going to be kind of stuck
at lower powered, still
pretty high powered, you know, like a thousand watt
processors, but it's kind of
stuck there in that region
for, you know, thermodynamic
reasons. So, really the
emphasis in the industry
is on the single-phase
direct-to-chip cooling because it's ready to scale.
We have a supply chain that's very well
robust worldwide.
We have liquid coolant suppliers
that are now able to provide high-quality
coolant worldwide. This is what
we need because we're at the
state where we're producing and consuming
hundreds of thousands of cold plates a month
and by next year that could climb
to maybe close to a million
cold plates a month. I mean, this is
crazy. You know, in 2022
we might have been talking about
100,000 cold plates a year, right?
In the whole industry. So,
something on that order, right? And
so, we're just scaling
super fast and right now
the technology that
can scale and keep up with it is single-phase
direct-to-chip.
For data centers,
connecting to the grid quickly means two
things. Building distributed energy
and having a plan for demand
flexibility. GridBeyond helps
with both. GridBeyond's DERMS and VPP
platform unlocks the potential
of distributed assets and dispatches
flexibility into the right market at the
right time. And this is more than
software. GridBeyond supports developers
every step of the way. From modeling
your highest ROI energy mix
to orchestrating the full set of assets around
a data center. The track record
speaks for itself. GridBeyond manages
over 1,400 sites
and more than 3.7 gigawatts of
load across Europe, the UK, and
the US. Learn more at
gridbeyond.com or click the link in the
show notes. If you work in energy
or climate, you already know the company's
antenna group has helped build. For three
decades, they've been the communications
and marketing partner behind the industry's
breakout companies, category
creators, and market leaders.
Today, their team is working across the most
consequential areas of the energy economy.
From data centers and grid
modernization, to nuclear, geothermal,
storage, critical materials,
and next generation technologies.
Antenna helps ambitious companies
become the names everyone in the market knows,
trusts, and wants to work with.
They build reputation, elevate executives,
drive demand, and turn momentum
into market leadership.
If your company is ready to lead its market,
Antenna is ready to help you get there.
Visit antennagroup.com.
When you harness the power of
millions of DERs in a VPP
and put artificial intelligence behind the
dispatch, the outcomes exceed
conventional generation. Energy
Hub's DERMS platform has been trained
on years of real dispatch data from over
2.6 million DERs
so utilities can plan with
confidence. That means consistent
load reduction across a four-hour event
window, even during the widest,
most uncertain peak periods.
Utilities target, shape, and verify
capacity down to the meter.
Unlock flexible capacity that costs
40-60% less to deploy
than traditional infrastructure in a
fraction of the time it takes you to break ground
on a peaker plant. Learn more at
energyhub.com.
Okay, so now
explain the relationship between
the cooling architecture
and water consumption.
What's the relationship between
the cooling architecture and
water consumption at the data center level?
They're actually kind of
disconnected.
And let me explain that.
What we want to do is break down
the journey of the heat
from the chip to the outside
into basically three
parts, right? We're going to have to
collect the heat from the servers
and then
move
that heat through
some fluid, air,
liquid, whatever,
to a
exchange point between
what we call the TCS, the technology
cooling system, which
is the part that collects the heat, to
the FWS, the facility water system,
which is the part that moves
the heat to the outside
heat rejection system.
And so the heat rejection system
is going to be whatever
devices that
the data center designer has chosen for
that climate, for that region, to be
chillers,
cooling towers,
dry coolers, whatever's
appropriate for that particular
region and power level.
And
ultimately,
that interface
between the TCS, the
cooling architecture that's collecting
the heat,
and the FWS is just a heat
exchanger, regardless of whether I've got two-phase
DLC, single-phase DLC,
or immersion. There is
typically a plate heat exchanger
that interfaces between the
two systems, and the FWS
doesn't care what was on the other side. What we
care about is having the
highest possible temperature
on the TCS rejecting
the heat to the FWS, because
I want to move the heat
from the processor, which is
the hottest point in the system, to the
outside. I want to try to move that heat downhill
the whole way. Then I can
just have thermodynamics carry the heat
out without requiring
an energy input other than pumps.
And that's the most efficient way to
move the heat out.
The challenge is that in
many climates, if the
outside temperature rises up above
100 degrees Fahrenheit, 43 degrees
Celsius,
that's pretty warm.
And that's actually warmer than
our FWS often wants
to be. And so that means
we have to push heat uphill, and then I need a
chiller. So what we're
doing is we're looking at the
climate, and we're
looking at the heat load, and we're
looking at how much
time are we spending
in the year
in a case where I'm having to push heat uphill.
And if it's just
a relatively small number of hours,
I might use something called an
adiabatic cooler. It's basically a dry cooler
with some pads, and they spray the pads
with water. This is oversimplifying.
My colleagues in the
heat rejection industry will
be great at that simplified
solution, but basically
it's actually an elegant solution
that allows me on those days
when I need to dump
heat out on a hot afternoon,
I can do so basically with just
a little bit of water and
do it very efficiently and get
that done. Other climates,
I'm going to spend half
the year requiring
pushing heat uphill,
and then I'm just going to need a refrigerated
chiller. And that uses a lot of energy.
So I
kind of went
a long ways from your original
question, but I
want to kind of disconnect. Our
goal is to
get the best technology on the TCS
that generates the
highest temperature
to feed the FWS, to feed
the highest temperature to the heat
rejection system so that I can use,
hopefully, the least amount of energy
to push that heat out into the environment.
So that all makes sense, but
then what does dictate the water?
consumption, the total water consumption
of a data center?
Sorry, I kind of
blew past that, because most
data centers don't use much water at all.
And they historically haven't used much water.
And
it's kind of frustrating that this
whole discussion is even going on.
But here's the deal.
When
we were air-cooling everything,
hyperscalers
who are building out thousands of
the same rack over
and over and over again,
their
biggest cost is energy
input to the data center. And so
they were looking at this and saying, well, the most
energy-efficient way for us
to cool this data
center is evaporating water.
And they
were elegant systems, they are elegant
systems, that used
kind of like I was describing earlier, basically
spraying a material, a filling
filler material, and blowing air
through it, using evaporation to cool that air
down. That's actually a smart
idea. It uses a relatively small amount
of water for the amount
of cooling power generated, or
the amount of cooling that's being done.
But, for those
select data centers,
it did consume, relatively speaking,
a lot of water, because I'm
cooling megawatts, right?
And so,
for every, I'm going to
use a kilogram of water for,
every two megawatts
or something like that. So,
over time,
in some communities, they paid attention
to this, and to be
frank, the hyperscalers were very
transparent about this. Google, Meta,
Microsoft, very transparent.
They were honest about the amount of water they were using.
That has kind of come back to
now,
I don't want to be over-negative,
people should be concerned about this, people
should be paying attention to these things. I don't want to be
negative on that point, but
the problem is, the data
centers we're building today aren't like that.
We're not cooling everything
with water like
that. Even when we're using a
cooling tower, we're frequently
pairing the cooling towers with dry coolers.
So, we're only using the cooling towers to
trim the heat rejection
on those hottest afternoons.
So,
as far as how much
water consumption is there, I don't know
that number precisely, because
every data center is going to be different.
Most data centers are built
completely closed-loop with no cooling
towers even, no evaporation.
Some are built with, like I said,
some evaporation on the hottest afternoons
just for a few hours a year, or
maybe tens of hours a year.
Others are more dependent
on cooling towers,
but they're using it more
for trim cooling, or just
the watts that need to be cooled on those
hottest afternoons.
And so,
what we do know
is that,
the hotter the water,
so using a cold plate
and direct liquid cooling
at the TCS
gives me hotter water
to the FWS,
which gives me more options
on the heat rejection, which allows me
to use less water if I have to use water at all.
So, the lesson here
is do the best I can collecting heat
so that
I can be as energy
efficient rejecting the heat
as possible.
So, I guess it'd be interesting maybe to separate out then,
you know, clearly what has happened over time
is that data centers
have, more recent data centers
are consuming less water on net.
You could make the case that they were never consuming
that much water, but it's like all
a matter of perspective. Either
way, on a relative basis, they're consuming less now.
And it seems like you've given
sort of two reasons
for that to be true. One is
a different optimization,
basically, where like early on,
the hyperscalers were optimizing predominantly
for energy consumption. If you're optimizing for energy
consumption, then you do adiabatic cooling
or whatever and do use some water.
And now, if you're optimizing a little bit more
for low water consumption,
then you just choose a different method of cooling
and you use less.
That's one reason. The other reason
being the sort of technical thing that you described
of like getting higher temperatures
in the TCS so that you have less
heat to reject. I don't know
if it's possible to separate those two from
each other, but like how much of the
change in overall water consumption
in modern data centers versus
previous generation data centers do you think
is from this re-optimization
versus the
technical advantage of a higher temperature TCS?
I would say
that a large percentage is
using direct liquid cooling
or more efficient
TCS
technology. Because
if I'm air
cooling and I'm not consuming
water to do that air cooling
in the data center, I'm
requiring cold water there
to generate
the cold air. I've got to have cold water
going through the heat exchangers to generate the cold air.
And that's going
to mean that I'm going to need chillers.
And the most efficient way to run the chillers
is often,
depending again on the climate and many other
things, is often with a cooling tower
providing cool water to the chillers
so the chillers are consuming less energy
but I am consuming some water.
So it's all connected to this
balance, as you noted, between
water usage and energy. But if I
start by
picking up heat
with 45 degrees C water
at the chip
and then my return
is 55 degrees C
I mean that's 135
or something Fahrenheit, I don't remember
the exact conversion.
I can reject that heat
in most places except the worst
day in, you know, middle
of India in the summer.
I can reject that
outside relatively
easily, right? And so
that has made it
without the use of consuming
water or, you know,
a whole lot of energy even.
So that's just made a huge difference.
As we moved into this AI
deployment
and it's one of the reasons why
Vincent makes a pretty big deal about this
in his keynotes
is it's enabled
this build out to
occur with, you know,
optimizing the
whole supply chain, whether it's chillers,
whether it's dry coolers, or whether it's water consumption.
So
that said, I do
want to come back to the fact that
these are really large data centers
and some of them have
really huge piping infrastructure
and there's a certain amount of water
required to fill all those pipes
and during the installation
and startup, we have to
flush and clean those pipes and that
does use water.
Now, it's not all consumed.
Initially, I can say
we were probably dumping a lot of
that water, but now
and just, again, remember this is
happening over a relatively short time
period of a few years,
now you'll find that most of the companies
are pretty sophisticated about that. They have pumping
stations that come out and they are
reusing the water, they're refiltering
it on-site
often, so that there's
very little wasted water. But that
and so
it's still likely that
there's water used from the local
water supply to
do the filling and cleaning
but even then, it's not always from the local water supply.
It's coming, you know, that
water may be trucked in from, you know,
Lexington, Kentucky, where one plant is
and from, you know, wherever, right?
And so, there's just not
a really
strong correlation to the
water being used to fill
and operate a data center
and actually where it's being drawn from.
And so,
again,
it's a
issue with a whole lot of variables
to it, and I don't want to say
that a community that's concerned about water
and has seen their water
table drop, that they're not seeing
an issue. I don't want to claim that.
You know, they must be wrong.
On the flip side,
I think if you dig deeper,
there's probably many, many reasons for that, right?
And
it's not, it's possibly
not because of the data center solely
or it's possibly not because of the cooling system.
It may be that
that water is used to build the roads
to the data center, so maybe the data center is still responsible
but, you know, it's not
a continuing use. All I have to say is
this is a complicated question, but
on the whole, water use in data centers
is pretty low compared to
many other sources
of consumption, and we
are continually innovating,
and I believe making more
efficient power and cooling systems
such that we're consuming less water
for the power that we're
using. I guess to ask
you a final question that maybe steps
one degree outside of your area of expertise
because it gets more into this, like,
question of community acceptance.
You know, I think this conversation
has, um,
has clarified why
this is challenging, because
on one hand, you can look
at the raw numbers of, like, how much
water have data centers consumed
historically and then currently, and again
those numbers are changing, like, it's
falling, the numbers are falling, but you can look at the raw
numbers, but, you know,
this concern that has arisen
and the fact that
water consumption, perception
of water consumption is one of the
two or three big issues right now in the
sort of data center backlash.
I think it's difficult to combat
given
the nuance associated with
it. It would be easy
If it weren't nuanced, and if every new data center could just say, I promise zero net water consumption, right?
But in the absence of that, and here's how I'm going to do it.
But in the absence of that, it's complicated.
And it's like one of these things that political messaging doesn't do a good job of describing.
So I wonder if you have a view on either from a technical and architectural perspective, like should modern hyperscale data centers all do X, Y, or Z?
Or from a messaging perspective, what is the right way to communicate the relationship between data centers and water consumption moving forward?
A tough question for sure.
But in the past year, I would say, you know, Microsoft has been a great example of messaging.
They got out front of this question.
They were very aggressive in messaging to the community in Wisconsin, where they were building a large data center.
I felt that they were messaging.
They were messaging very clearly how they were going to cool and how much water they intended to use and how they were, you know, achieving this.
So kind of doing what you suggested there, unfortunately, I still see a backlash to that data center.
And I still see water being brought up as a point.
And my feeling is that that, number one, I think it's table stakes to take the approach that.
Microsoft did in that case.
And I think as an industry, I think we're getting better about that.
Maybe a little too slowly, but I think we're getting better about being really transparent in the communications.
I think we could do better literally just inviting community in to see how this works, if that's possible.
There's a whole lot of safety and other things and some privacy concerns.
But, you know, I think that would help people see, OK, I get this.
On the other hand, I think being honest about, hey, building a great big building that's going to consume 500 megawatts of power just uses water.
It does.
Whether it's just keeping the dust on the construction site down or preparing the roads or, you know, pouring the concrete, whatever, right?
It's going to consume water.
And so there's going to be a period.
Where water is consumed, building a huge data center campus and communicating that might help.
But overall, this is an opinion or a belief.
Again, this isn't my area of expertise, but, you know, I'm in the waters like you are.
And seeing that, I wonder if a lot of this just isn't a general feeling of discomfort of this new technology that's being built out all around.
I think we're all uncertain about how it's going to play out.
And it's pretty easy to take it out on these big nondescript buildings being built and consuming resources, right?
And so I think what we can do as an industry is continually perform outreach, try to explain what we're doing, be as transparent as possible, try to get away from all the NDAs.
I understand sometimes why they're there.
That just breeds distrust.
And we all know that.
Again, I understand the reason for that sometimes.
But just being transparent.
And then there's not much we can do about communication about AI and its application these days.
That depends on a few loud voices that you and I don't have any control over.
But, you know, but really trying to work as an industry to be transparent and hopefully bring focus on the applications that people do like.
I think, you know, autonomous vehicles and autonomous taxis are being used in a huge number of communities.
And a lot of people really like them.
You know, Waymo and cyber taxis now and other options.
Those wouldn't be possible without these data centers.
And, of course, all the functions on our phones and whatnot.
So don't need to go down that path.
But so it's I think this ends up being more of a human issue than a technical issue.
Even then, a communications issue.
And it's going to take a little while to resolve.
But transparency, I think, is the first step.
All right, Tim.
This was really interesting.
Very much appreciate your time.
Thank you.
Tim Shedd is the founder of Abulian Insights.
This show is a production of Latitude Media.
You can head over to LatitudeMedia.com for links to today's topics.
This episode is produced by Max Savage-Levinson.
Mixing and theme song by Sean Marquand.
Anne Bailey edits the video version of the show.
Stephen Lacey is our host.
He's our executive editor.
All of our episodes are on YouTube.
Subscribe to Latitude Media for episodes of this show and Open Circuit.
You can also find the audio version of the show and not have to look at my face anywhere you get your audio podcasts.
I'm Shail Khan.
This is Catalyst.
Podcast Summary
Key Points:
Modern data centers use significantly less water than in the past due to advances in cooling technologies, especially direct-to-chip liquid cooling.
Historical water usage was driven by evaporative cooling systems, which consumed more water for energy efficiency, but today’s designs prioritize higher-temperature heat rejection to reduce reliance on water.
The shift from air cooling to closed-loop liquid cooling allows data centers to reject heat more efficiently, often eliminating or minimizing evaporative water use.
Water consumption today is primarily associated with construction, pipe flushing, and initial operations, not ongoing operations, and most sites reuse water to minimize waste.
The perception of data centers as major water users is often disproportionate to reality, especially when compared to agriculture or other large consumers.
Transparency in communication—such as disclosing water use and cooling methods—helps build community trust and reduces backlash.
Cooling architecture directly influences water use
The industry is moving toward greater transparency and outreach, recognizing that water concerns stem more from public perception than actual consumption.
Summary:
Modern data centers consume far less water than previously believed, largely due to technological advancements like direct-to-chip liquid cooling and closed-loop systems. Historically, evaporative cooling used significant water for energy efficiency, but today’s designs prioritize high-temperature heat rejection, reducing the need for water-intensive cooling towers. Most data centers now operate with minimal evaporation, relying instead on efficient heat transfer and dry coolers for peak loads.
While construction and startup phases require some water for pipe filling and cleaning, this is typically reused on-site, minimizing environmental impact. The perception that data centers drain aquifers stems from outdated numbers and misaligned context—agriculture and urban development consume far more water. The industry acknowledges that transparency in communication is key to easing community concerns, as demonstrated by Microsoft’s proactive messaging in Wisconsin.
Ultimately, data center water use is a small fraction of broader water consumption, and the future lies in continued innovation, efficiency, and public education to address misconceptions and build trust.
FAQs
No, modern data centers use very little water. Most are now built with closed-loop cooling systems that minimize or eliminate evaporation, and only use water during installation or for short-term trim cooling on hot days.
Water usage has decreased significantly over time. Early data centers relied on evaporative cooling, which used more water. Today’s designs prioritize efficiency and use advanced cooling technologies that reduce water consumption on a relative scale.
Modern data centers use direct-to-chip liquid cooling, in-row coolers, and closed-loop systems. These technologies allow for highly efficient heat removal with minimal water use, especially compared to older evaporative cooling methods.
No, liquid cooling does not require large amounts of water. While it involves plumbing, the system is designed to be closed-loop, meaning water is reused and not consumed. Most of the water used is during installation and cleaning, not ongoing operations.
Better cooling architectures—like direct liquid cooling—allow data centers to reject heat at higher temperatures, reducing the need for water-intensive chiller systems and enabling more efficient heat rejection with less water use.
Yes, companies like Microsoft are leading in transparency by clearly communicating their water usage and cooling strategies to local communities, helping build trust and address concerns directly.
Chat with AI
Loading...
Pro features
Go deeper with this episode
Unlock creator-grade tools that turn any transcript into show notes and subtitle files.